19 changes: 17 additions & 2 deletions specification/source/sequenceDocumentation.rst
Original file line number Diff line number Diff line change
Expand Up @@ -84,7 +84,7 @@ Microsoft Word document using the following procedure.

As an example, consider the following snippet of a composite control block.

.. code-block:: modelica
.. code-block::
HigMassSupplyTemperature_TRoom con(TSubSet_max=303.15, final TSubSet_min=293.15);
Expand All @@ -98,6 +98,12 @@ As an example, consider the following snippet of a composite control block.
final unit="K",
displayUnit="degC") = 293.15 "Minimum heating supply water temperature";
parameter Controls.OBC.CDL.Types.SimpleController
controllerType = Buildings.Controls.OBC.CDL.Types.SimpleController.P
"Type of controller" annotation (Dialog(group="Control gains"));
... [omitted]
annotation(
Documentation(
info="<html>
Expand All @@ -108,7 +114,7 @@ As an example, consider the following snippet of a composite control block.
The controller tracks the room temperature set point <code>TRooSet</code> by
adjusting the supply water temperature set point <code>TSupSet</code> linearly between
<code>TSupSetMin</code> and <code>TSupSetMax</code>
...
PI-controller likely saturate due to the slow system response.
</p>
</html>"
Expand All @@ -134,11 +140,13 @@ As an example, consider the following snippet of a composite control block.
src="modelica://Buildings/Resources/Images/Controls/OBC/RadiantSystems/Heating/HighMassSupplyTemperature_TRoom.png"/>
</p>
<p>
<-- cdl(visible=(not (controllerType is final))) or controllerType <> CDL.Types.SimpleController.P -->
<b>Note:</b>
For systems with high thermal mass, this controller should be left configured
as a P-controller, which is the default setting.
PI-controller likely saturate due to the slow system response.
</p>
<-- end cdl -->
</html>"
)
)
Expand All @@ -152,9 +160,16 @@ For this control block, ``modelica-json`` will produce content for the Word desc
``TSupSetMin`` (:math:`=20^\circ`) and ``TSupSetMax`` (:math:`=30^\circ` adjustable)
based on the output signal of the proportional controller..."

Note that ``modelica-json`` removes the notice at the end of the sequence description
if the ``controllerType`` is
declared as ``final`` (because then, no other choice can be made).
Through this mechanism, sections and images can be removed or enabled in the generated
sequence description.

To use IP units, ``modelica-json`` will have a configuration that specifies what units should be used.
The documentation will also include the figure as declared in the CDL specification.


The Control Sequence Selection and Configuration tool could make the section
``annotation(__CDL(Documentation(info=STRING)))`` editable, thereby allowing
users to customize the description of the sequence and add any other desired documentation.