11 changes: 11 additions & 0 deletions CHANGELOG.md
Original file line number Diff line number Diff line change
Expand Up @@ -14,6 +14,11 @@ Changes since the repository went public on 23 October 2026, up to feature catal

### Added

- `project_save` saves an open project in a worker-owned instance (no recovery archive; read-only projects and unresolved changes are refused), the step between `simulation_download` and credential provisioning (catalog `0.4.186`, unverified).
- `host_build_identity` reports the `sourceCommit` and `sourceTreeDirty` a bundle was packaged from; isolated builds and bundle manifests now record them.
- `target_capabilities` reports `plc_loadable_generate` per PLC from a `LoadableProvider` probe.
- `simulation_provision_status` lists credential-provisioning attempts with their stage and the exact next calls; `simulation_provision_recover` runs detach, an empty owned Portal, the reconciliation and the reopen in one call (catalog `0.4.187`, unverified).
- **WinCC Unified runtime alarms:** `runtime_unified_*` logs in to a Unified PC Runtime's GraphQL server with a protected credential and a pinned certificate, reads active and logged alarms in the UMC user's language and acknowledges alarms by their qualified path on a runtime on this PC after an explicit acknowledgement ([reference](docs/reference/unified-runtime-alarms.md)). Not run natively yet.
- `call_parameter_set`, `graphical_operand_set`, `graphical_network_patch` and `graphical_network_insert` accept `items` (one block per item, one checkpoint, compile and save, a structured readback per item).
- `hmi_inspect` takes `excludeSystem` (section=model without system tags, system text lists and OPC UA alarm types) and `rowMode: "compact"` (path and `contentSha256` only), and returns `sectionContentSha256` for model rows.
- `project_snapshot_capture` reports its stage in progress notifications and returns `remoteAccess` with the review's `tia://` resource URI or the chunked `artifact_read` route.
Expand Down Expand Up @@ -195,6 +200,10 @@ Changes since the repository went public on 23 October 2026, up to feature catal

### Changed

- `simulation_download` reports `projectModifiedAfter`, `saveRequiredBeforeProvisioning` and `nextStep`; `UnsavedProject` from provisioning, `SimulationProvisionStorageCollision` and `SimulationRegistrationsPresent` carry remediations; `ResourceBusy` lists `blockingAdmissions` with each operation and its reconciliation tool (`simulation_provision_reconcile` for a failed provisioning).
- `tia_detach` reports PLCSIM instances that stay registered (`plcsimRegistrations`) when the worker used the PLCSIM API.
- Change views carry `projectSave` (`isModifiedAtPrepare`, `savedBeforeApply`, `savedAfterApply`), since `preview.isModified` stays the prepare-time state.
- `project_inventory` explains `completeness.complete` (always false) versus `scopeComplete`; the `sim_tags`, provisioning TLS-trust and `plc_loadable_generate` descriptions state their limits.
- `--timeout-seconds` accepts up to 3600 s (was 900), in the Host and the launcher scripts.
- A failed `simulation_download` reports `ticketState` (`reusable`, `spent`, `unusable`) and a remediation; `FreshSimulationStorageRequired` says the ticket was spent.
- An explicit HMI `target.kind` that the operation or `hmi_inspect` section cannot take is refused before the preservation capture.
Expand Down Expand Up @@ -300,6 +309,8 @@ Changes since the repository went public on 23 October 2026, up to feature catal

### Fixed

- **Quoted simulator symbols:** `"Db".A` returned `DoesNotExist` when the PLCSIM tag list spells it `Db.A`; symbolic reads and writes now pass the tag list's spelling. Not run natively yet.

- **Clearer dependency refusal on an F-CPU:** when TIA refuses to export a block during the delete dependency scan, `DependencyCoverageIncomplete` now names the block's programming language, know-how protection and consistency. On a PLC with a safety program this is the generated `FOB_RTG1` (a know-how protected SCL OB), whose native cross-references name no references either, so `tag_delete`, `constant_delete`, `type_delete` and `block_delete` stay refused there by decision (`local.safety.drive-tags-bool.20261112`).

- **Classic screen edit when the HMI compiler cannot run:** on 11 November 2026 the compile after a `hmi_classic_screen_edit` import and the rollback compile both ended with `Cannot compile. Cannot access the project path.`, and the change reported "Rollback compiler diagnostics do not match the successful baseline". Both compiles now report a compiler that could not run (`compile.compilerUnavailable`, `hmiEvidence.rollbackCompilerUnavailable`); after such a rollback compile the worker still compares every regular screen and states that the open project holds the original screens unsaved, and whether the saved project is the checkpoint or, after the apply's own save, the edit. The change stays `recovery_required`. `hmiEvidence.baselineCompileSkippedGeneration` records a baseline that V21 answered from its last compile. The cause of the compiler failure is not identified and it is still detected only after the import; see the [record](docs/verification/classic-screen-compile-path-failure-20261111.md).
Expand Down
6 changes: 4 additions & 2 deletions README.md
Original file line number Diff line number Diff line change
Expand Up @@ -205,8 +205,10 @@ adapter-owned simulator instances. Online access to real PLCs (compare, station
upload, download) exists only behind the off-by-default `--physical-plc-online`
Host option, is not qualified on physical hardware and never answers logins or
passwords; force and CPU mode control are not exposed
([real PLCs](docs/reference/physical-plc-online.md)). Keep project exports and
credentials private.
([real PLCs](docs/reference/physical-plc-online.md)). Alarms of a WinCC Unified PC
Runtime can be read, and acknowledged only on a runtime on the same PC after an
explicit acknowledgement ([Unified alarms](docs/reference/unified-runtime-alarms.md));
nothing else is written to an HMI runtime. Keep project exports and credentials private.