Expand Up @@ -51,38 +51,36 @@ model Effectiveness
annotation (Placement(transformation(extent={{100,-50},{120,-30}})));

protected
Real rat
"Ratio of the average operating volumetric air flow rate to the nominal supply air flow rate";
Real epsSenPL
"Part load (75%) sensible heat exchanger effectiveness used for calculation";
Real epsSen_nominal
"Nominal sensible heat exchanger effectiveness used for calculation";
Real epsLatPL
"Part load (75%) latent heat exchanger effectiveness used for calculation";
Real epsLat_nominal
"Nominal latent heat exchanger effectiveness used for calculation";
Real rat
"Ratio of the average operating volumetric air flow rate to the nominal supply air flow rate";
Real epsSenPL
"Part load (75%) sensible heat exchanger effectiveness used for calculation";
Real epsSen_nominal
"Nominal sensible heat exchanger effectiveness used for calculation";
Real epsLatPL
"Part load (75%) latent heat exchanger effectiveness used for calculation";
Real epsLat_nominal
"Nominal latent heat exchanger effectiveness used for calculation";

equation
// check if the air flows are too unbalanced.
assert(VSup_flow - 2*VExh_flow < 0 or VExh_flow - 2*VSup_flow < 0,
"Unbalanced air flow ratio",
assert(noEvent(VSup_flow - 2*VExh_flow < 0) or noEvent(VExh_flow - 2*VSup_flow < 0),
"***Warning in " + getInstanceName() + ": The ratio of the supply flow rate to the exhaust flow rate should be in the range of [0.5, 2].",
level=AssertionLevel.warning);
// calculate the average volumetric air flow and flow rate ratio.
rat = (VSup_flow + VExh_flow)/2/VSup_flow_nominal;
// check if the extrapolation goes too far.
assert(rat > 0.5 and rat < 1.3,
"Operating flow rate outside the full accuracy range",
assert(noEvent(rat > 0.5) and noEvent(rat < 1.3),
"Warning in " + getInstanceName() + ": The ratio of the operating flow rate to the nominal supply flow rate should be in the range of [0.5, 1.3].",
level=AssertionLevel.warning);
// switch between cooling and heating modes based on the difference between the supply air temperature and the exhaust air temperature.
epsSenPL = Buildings.Utilities.Math.Functions.regStep(TSup-TExh, epsSenCooPL, epsSenHeaPL, 1e-5);
epsSen_nominal = Buildings.Utilities.Math.Functions.regStep(TSup-TExh, epsSenCoo_nominal, epsSenHea_nominal, 1e-5);
epsLatPL = Buildings.Utilities.Math.Functions.regStep(TSup-TExh, epsLatCooPL, epsLatHeaPL, 1e-5);
epsLat_nominal = Buildings.Utilities.Math.Functions.regStep(TSup-TExh, epsLatCoo_nominal, epsLatHea_nominal, 1e-5);
// calculate effectiveness.
epsSen =wheSpe*(epsSenPL + (epsSen_nominal - epsSenPL)*(rat -
0.75)/0.25);
epsLat =wheSpe*(epsLatPL + (epsLat_nominal - epsLatPL)*(rat -
0.75)/0.25);
epsSen =wheSpe*(epsSenPL + (epsSen_nominal - epsSenPL)*(rat - 0.75)/0.25);
epsLat =wheSpe*(epsLatPL + (epsLat_nominal - epsLatPL)*(rat - 0.75)/0.25);
assert(epsSen > 0 and epsSen < 1,
"Insensed value for the sensible heat exchanger effectiveness",
level=AssertionLevel.error);
Expand All @@ -102,7 +100,8 @@ under heating and cooling modes at different flow rates of the supply
air and the exhaust air.
</p>
<p>
It firstly calculates the average volumetric flow rate through the heat exchanger by:
It firstly calculates the ratio of the average volumetric flow rate to the nominal
supply flow rate by:
</p>
<pre>
rat = (VSup_flow + VExh_flow)/(2*VSup_flow_nominal),
Expand Down

0 comments on commit 29e2b79