4 changes: 2 additions & 2 deletions Annex60/Fluid/HeatExchangers/ActiveBeams/Data/Trox.mo
Original file line number Diff line number Diff line change
@@ -1,6 +1,6 @@
within Annex60.Fluid.HeatExchangers.ActiveBeams.Data;
package Trox "Performance data for Trox"
record DID632A_nozzleH_lenght6ft_cooling =
record DID632A_nozzleH_length6ft_cooling =
Annex60.Fluid.HeatExchangers.ActiveBeams.Data.Generic (
primaryAir(
r_V = {0,0.714286, 1,1.2857},
Expand Down Expand Up @@ -38,7 +38,7 @@ Performance data for Trox active beam for cooling mode.
</html>"));


record DID632A_nozzleH_lenght6ft_heating =
record DID632A_nozzleH_length6ft_heating =
Annex60.Fluid.HeatExchangers.ActiveBeams.Data.Generic (
dT(
f = {0,0.5,1},
Expand Down
Original file line number Diff line number Diff line change
Expand Up @@ -92,9 +92,9 @@ model CoolingAndHeating
redeclare package MediumWat = MediumW,
redeclare package MediumAir = MediumA,
redeclare
Annex60.Fluid.HeatExchangers.ActiveBeams.Data.Trox.DID632A_nozzleH_lenght6ft_cooling perCoo,
Annex60.Fluid.HeatExchangers.ActiveBeams.Data.Trox.DID632A_nozzleH_length6ft_cooling perCoo,
redeclare
Annex60.Fluid.HeatExchangers.ActiveBeams.Data.Trox.DID632A_nozzleH_lenght6ft_heating perHea,
Annex60.Fluid.HeatExchangers.ActiveBeams.Data.Trox.DID632A_nozzleH_length6ft_heating perHea,
energyDynamics=Modelica.Fluid.Types.Dynamics.SteadyStateInitial)
"Active Beam"
annotation (Placement(transformation(extent={{26,48},{54,72}})));
Expand Down
Original file line number Diff line number Diff line change
Expand Up @@ -69,7 +69,7 @@ model CoolingOnly
redeclare package MediumWat = MediumW,
redeclare package MediumAir = MediumA,
redeclare
Annex60.Fluid.HeatExchangers.ActiveBeams.Data.Trox.DID632A_nozzleH_lenght6ft_cooling perCoo,
Annex60.Fluid.HeatExchangers.ActiveBeams.Data.Trox.DID632A_nozzleH_length6ft_cooling perCoo,
energyDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial) "Active beam"
annotation (Placement(transformation(extent={{26,48},{54,72}})));
equation
Expand Down
Original file line number Diff line number Diff line change
Expand Up @@ -78,9 +78,9 @@ model HeatingOnly
redeclare package MediumWat = MediumW,
redeclare package MediumAir = MediumA,
redeclare
Annex60.Fluid.HeatExchangers.ActiveBeams.Data.Trox.DID632A_nozzleH_lenght6ft_cooling perCoo,
Annex60.Fluid.HeatExchangers.ActiveBeams.Data.Trox.DID632A_nozzleH_length6ft_cooling perCoo,
redeclare
Annex60.Fluid.HeatExchangers.ActiveBeams.Data.Trox.DID632A_nozzleH_lenght6ft_heating perHea,
Annex60.Fluid.HeatExchangers.ActiveBeams.Data.Trox.DID632A_nozzleH_length6ft_heating perHea,
energyDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial) "Active beam"
annotation (Placement(transformation(extent={{26,48},{54,72}})));
equation
Expand Down
2 changes: 1 addition & 1 deletion Annex60/Fluid/HeatExchangers/ActiveBeams/UsersGuide.mo
Original file line number Diff line number Diff line change
Expand Up @@ -130,7 +130,7 @@ The model can be configured to be steady-state or dynamic.
If configured as dynamic, then a dynamic conservation equation is applied to the water streams
for heating and for cooling.
However, because the capacity of the beam depends on its inlet temperature, and is independent of the
outlet temperature, the heat transfered
outlet temperature, the heat transferred
to the room at the port <code>heaPor.Q_flow</code>, as well as the heat added to or removed from the
water streams, will instantaneously change.
The only dynamic responses are the water outlet temperatures, which change with a first
Expand Down
Original file line number Diff line number Diff line change
Expand Up @@ -58,9 +58,9 @@ model NumberOfBeams
redeclare package MediumWat = MediumW,
redeclare package MediumAir = MediumA,
redeclare
Annex60.Fluid.HeatExchangers.ActiveBeams.Data.Trox.DID632A_nozzleH_lenght6ft_cooling perCoo,
Annex60.Fluid.HeatExchangers.ActiveBeams.Data.Trox.DID632A_nozzleH_length6ft_cooling perCoo,
redeclare
Annex60.Fluid.HeatExchangers.ActiveBeams.Data.Trox.DID632A_nozzleH_lenght6ft_heating perHea,
Annex60.Fluid.HeatExchangers.ActiveBeams.Data.Trox.DID632A_nozzleH_length6ft_heating perHea,
nBeams=1,
energyDynamics=Modelica.Fluid.Types.Dynamics.SteadyState)
"Active beam"
Expand Down Expand Up @@ -102,10 +102,10 @@ model NumberOfBeams
redeclare package MediumWat = MediumW,
redeclare package MediumAir = MediumA,
redeclare
Annex60.Fluid.HeatExchangers.ActiveBeams.Data.Trox.DID632A_nozzleH_lenght6ft_cooling
Annex60.Fluid.HeatExchangers.ActiveBeams.Data.Trox.DID632A_nozzleH_length6ft_cooling
perCoo,
redeclare
Annex60.Fluid.HeatExchangers.ActiveBeams.Data.Trox.DID632A_nozzleH_lenght6ft_heating
Annex60.Fluid.HeatExchangers.ActiveBeams.Data.Trox.DID632A_nozzleH_length6ft_heating
perHea,
nBeams=nBeams,
energyDynamics=Modelica.Fluid.Types.Dynamics.SteadyState)
Expand Down
2 changes: 1 addition & 1 deletion Annex60/Resources/www/modelicaDoc.css
Original file line number Diff line number Diff line change
Expand Up @@ -299,7 +299,7 @@ table.navigation {
margin-top: 2em;
}

.seperator {
.separator {
color: gray;
}

Expand Down
Original file line number Diff line number Diff line change
Expand Up @@ -44,7 +44,7 @@ equation
info="<html>
<p>This model is a variant of the calculations defined in
VDI 6007 Part 1. It adds a second equivalent air temperature for windows in
case heat transfer through windows and exterior walls is handled seperately in
case heat transfer through windows and exterior walls is handled separately in
the Reduced Order Model. The sum of all weightfactors for windows should be
one as well as the sum for all wall elements.</p>
</html>"));
Expand Down
Original file line number Diff line number Diff line change
Expand Up @@ -44,7 +44,7 @@ in TMY weather data sets (radiation from the environment is missing), the
influence of this temperature is not considered in the presented
models. It is in any case a minor effect as black-body sky temperature and
environmental radiative temperature hardly differ. Furthermore, the Guideline
VDI 6007 Part 1 calculates the correction term for each orientation seperately
VDI 6007 Part 1 calculates the correction term for each orientation separately
with individual radiative and convective coefficients of heat transfer. In the
presented models, the user can define only one radiative and one convective
coefficient of heat transfer. When using area-weighted coefficients, the impact
Expand Down
Original file line number Diff line number Diff line change
Expand Up @@ -301,7 +301,7 @@ equation
Solar radiation on tilted surface is calculated using models of
Annex60. The thermal zone is a simple room defined in Guideline
VDI 6007 Part 1 (VDI, 2012). All models, parameters and inputs
except sunblinds, seperate handling of heat transfer through
except sunblinds, separate handling of heat transfer through
windows, an extra wall element for ground floor (with additional
area), an extra wall element for roof (with additional area) and
solar radiation are similar to the ones defined for the
Expand Down
Original file line number Diff line number Diff line change
Expand Up @@ -239,7 +239,7 @@ equation
Solar radiation on tilted surface is calculated using models of
Annex60. The thermal zone is a simple room defined in Guideline
VDI 6007 Part 1 (VDI, 2012). All models, parameters and inputs
except sunblinds, seperate handling of heat transfer through
except sunblinds, separate handling of heat transfer through
windows, no wall element for internal walls and solar radiation
are similar to the ones defined for the guideline&apos;s test
room. For solar radiation, the example relies on the standard
Expand Down
Original file line number Diff line number Diff line change
Expand Up @@ -269,7 +269,7 @@ equation
Solar radiation on tilted surface is calculated using models of
Annex60. The thermal zone is a simple room defined in Guideline
VDI 6007 Part 1 (VDI, 2012). All models, parameters and inputs
except sunblinds, seperate handling of heat transfer through
except sunblinds, separate handling of heat transfer through
windows, an extra wall element for ground floor (with additional
area) and solar radiation are similar to the ones defined for the
guideline&apos;s test room. For solar radiation, the example
Expand Down
Original file line number Diff line number Diff line change
Expand Up @@ -245,7 +245,7 @@ equation
Solar radiation on tilted surface is calculated using models of
Annex60. The thermal zone is a simple room defined in Guideline
VDI 6007 Part 1 (VDI, 2012). All models, parameters and inputs
except sunblinds, seperate handling of heat transfer through
except sunblinds, separate handling of heat transfer through
windows and solar radiation are similar to the ones defined for
the guideline&apos;s test room. For solar radiation, the example
relies on the standard weather file in Annex60.</p>
Expand Down
Original file line number Diff line number Diff line change
Expand Up @@ -43,7 +43,7 @@ algorithm
unless the area is zero. It substracts the wall area <code>AExt</code>
for first entry in <code>AArray</code> and <code>AWin</code> for
second entry in AArray unless <code>AArray[1]</code> and/or
<code>AArray[2]</code> are not zero. This is done seperately for each
<code>AArray[2]</code> are not zero. This is done separately for each
orientation. Consequently, the function gives an <code>nRow x nCol</code>
array back as output. Each row stands for one area in
<code>AArray</code> and each row for one orientation in
Expand All @@ -62,7 +62,7 @@ algorithm
zeros with length 1.
For solar radiation through windows, the window and wall area with the same
orientation as the incoming radiation should be substracted as these areas
cannot be hit by the radiation. This needs to be done seperately for each
cannot be hit by the radiation. This needs to be done separately for each
orientation and for exterior walls and windows only, according to:
<p align=\"center\" style=\"font-style:italic;\">
SplitFac<sub>i,k</sub> = (AArray[i]
Expand Down
6 changes: 3 additions & 3 deletions Annex60/ThermalZones/ReducedOrder/RC/OneElement.mo
Original file line number Diff line number Diff line change
Expand Up @@ -147,14 +147,14 @@ model OneElement "Thermal Zone with one element for exterior walls"
final splitFactor=splitFactor,
final nOut=dimension,
final nIn=1) if ATot > 0
"Splits incoming internal gains into seperate gains for each wall element,
"Splits incoming internal gains into separate gains for each wall element,
weighted by their area"
annotation (Placement(transformation(extent={{210,76},{190,96}})));
BaseClasses.ThermSplitter thermSplitterSolRad(
final splitFactor=splitFactorSolRad,
final nOut=dimension,
final nIn=nOrientations) if ATot > 0 and sum(ATransparent) > 0
"Splits incoming solar radiation into seperate gains for each wall element,
"Splits incoming solar radiation into separate gains for each wall element,
weighted by their area"
annotation (Placement(transformation(extent={{-138,138},{-122,154}})));
BaseClasses.ExteriorWall extWallRC(
Expand All @@ -180,7 +180,7 @@ protected
"Share of each wall surface area that is non-zero";
parameter Real splitFactorSolRad[dimension, nOrientations]=
BaseClasses.splitFacVal(dimension, nOrientations, AArray, AExt, AWin)
"Share of each wall surface area that is non-zero, for each orientation seperately";
"Share of each wall surface area that is non-zero, for each orientation separately";
Modelica.Thermal.HeatTransfer.Components.Convection convExtWall if ATotExt > 0
"Convective heat transfer of exterior walls"
annotation (Placement(transformation(extent={{-114,-30},{-94,-50}})));
Expand Down
12 changes: 6 additions & 6 deletions Annex60/ThermalZones/ReducedOrder/RC/package.mo
Original file line number Diff line number Diff line change
Expand Up @@ -69,7 +69,7 @@ package RC
</p>
<p>
Heat transfer through windows and solar radiation transmission are handled
seperately. One major difference in the implementations in this
separately. One major difference in the implementations in this
package compared to the guideline is an additional element for heat transfer
through windows, which are lumped with exterior walls in the guideline VDI 6007
Part 1 (VDI, 2012). The heat transfer element for the windows allows to model
Expand All @@ -79,11 +79,11 @@ package RC
exterior walls leads to a virtual capacity for the windows and results in a
shifted reaction of the room temperature to environmental impacts
(Lauster, Bruentjen <i>et al.</i>, 2014).
However, the user is free to choose whether keeping windows seperately
However, the user is free to choose whether keeping windows separately
(<code>AWin</code>) or merging them (<code>AExt=AExterior+AWindows, AWin=0</code>).
The window areas can be defined seperately for solar
The window areas can be defined separately for solar
radiation (vector <code>ATransparent</code>) and heat transfer
(vector <code>AWin</code>). For cases where the windows are kept seperately,
(vector <code>AWin</code>). For cases where the windows are kept separately,
<code>ATransparent</code> and <code>AWin</code> are equal. When merging
windows and exterior walls, <code>AWin</code> can be set to zero while
<code>ATransparent</code> still represents the actual window area for solar
Expand Down Expand Up @@ -142,7 +142,7 @@ package RC
one for convective and one for radiative gains. Considering solar radiation
typically requires several models upstream to calculate angle-dependent
irradiation or solar absorption and reflection by windows.
We decided to keep these models seperate from the thermal
We decided to keep these models separate from the thermal
zone model. Thus, solar radiation is handled as a basic
<code>RadiantEnergyFluenceRate</code>.
For internal gains, the user might need
Expand All @@ -164,7 +164,7 @@ package RC
the area of exterior walls and windows with the same orientation as the incoming
radiation is not taken into account for the distribution as such surfaces cannot
be hit by the particular radiation. This calculation is performed for each
orientation seperately using
orientation separately using
<a href=\"Annex60.ThermalZones.ReducedOrder.RC.BaseClasses.splitFacVal\">
Annex60.ThermalZones.ReducedOrder.RC.BaseClasses.splitFacVal</a>.
</p>
Expand Down
Original file line number Diff line number Diff line change
Expand Up @@ -12,7 +12,7 @@ annotation (Documentation(info="<html>
exterior wall for the heavyweight construction.</p>
<p>Comparative results are supplied with the guideline and have been caclulated
using two different programs for electrical circuit calculations (for day 1,
10 and 60 in hourly steps). The validation procedure is orginally thought to
10 and 60 in hourly steps). The validation procedure is originally thought to
verifiy the correct implementation of an analytical calculation algorithm
defined in the guideline. For that, a range of max 0.1 K or max 1 W deviation
is allowed. As the implementation cannot reflect all aspects of the algorithm,
Expand Down
2 changes: 1 addition & 1 deletion Annex60/Utilities/Math/Functions/average.mo
Original file line number Diff line number Diff line change
Expand Up @@ -8,7 +8,7 @@ algorithm
y := sum(u)/nin;

annotation (Documentation(info="<html>
<p>This block outputs the average of the vector. </p>
<p>This function outputs the average of the vector. </p>
</html>", revisions="<html>
<ul>
<li>November 28, 2013, by Marcus Fuchs:<br/>
Expand Down