Smart Heating Control – reference

Română · README · Guide

Everything the integration does, in technical detail: what every rule, sensor, service and card option does. For a step by step introduction see the guide.

Features

  • Presence in three states: home, nearby (e.g. somewhere in your city) and far. Nearby zones are evaluated from coordinates too, so a zone such as "Office" inside the city counts as nearby and stale not_home states are corrected.

  • Schedules with workday / weekend / weekday / custom profiles, holidays from the Workday integration, profiles chosen from a calendar, a day boundary for night shifts, or an existing Schedule helper.

  • Optimal start / stop with a thermal model learned per room: heating, heat loss and thermal inertia (see Learning and Optimal stop). Once an optimal start begins it continues until the scheduled time, even if the room is warm early; the rules above the schedule can still override it.

  • Windows: open/close delays, frost protection or off, detection from a sudden temperature drop, windows of neighbouring rooms, alerts.

  • Weather: outdoor cutoff with averaging and hysteresis (the averaging time is also how long an outdoor value stays valid when the sensor or weather is unavailable; after it the outdoor temperature is unknown), heating season (dates or automatic), outdoor compensation, forecast, solar gain per room (needs the weather entity of the house; the setting is shown only when one is set). The measured average of the last Average over hours turns the heating off when it reaches the cutoff; the heating may run again when that average falls to the resume temperature (cutoff − hysteresis). With Use the forecast the mean forecast of the next Forecast hours also counts (never a single forecast hour):

    • heating off by the measured average, forecast mean at or below the resume temperature: the heating may run (a warm afternoon does not keep it off in a cold evening); forecast mean above the resume temperature: it stays off;
    • heating running, forecast mean at or above the cutoff: the heating is turned off earlier and stays off until that mean falls to the resume temperature (the same hysteresis as the measured average); a mean below the cutoff does not turn it off. More Forecast hours turn it off earlier before a warm period.

    In the mean each forecast value holds for its hour; until the next forecast hour the measured value counts. Cutoff, hysteresis, Average over and Forecast hours all come from the options. Without a forecast only the measured average decides.

  • Manual changes: detected automatically and kept for a fixed time or until the next reevaluation (schedule, presence, window or mode change). A device that only reports, later, the values the integration sent it (e.g. a sleepy Zigbee TRV) is not a manual change. If a higher rule (window, frost protection) changes the devices meanwhile, the manual value is set again afterwards. Child lock, pause and per-room / global clear buttons.

  • Global modes: Auto, Vacation (with dates, preheating before the return and automatic vacation), Off (frost protection) and Summer. During the preheating hours before the end of a vacation the schedule applies even while everyone is still far. Only an end date: the vacation starts now. The automatic vacation ends when someone is on the way home (arriving), so the house preheats; it comes back only when everyone has been far again for the time set in Automatic vacation after everyone is far for.

  • Energy: dynamic tariff, PV surplus, control of the heat source (boiler) from the heat demand of the rooms, heating time statistics.

  • Safety: frost protection always (once it starts heating it continues until the device stops asking for heat; a room in frost protection starts the heat source on its own, also while paused; with a room sensor it is decided from the room and the TRVs are boosted to open), maximum temperature, command verification with retry, alerts for unavailable devices, failed sensors, low batteries and open windows, valve exercise for TRVs.

  • Mold risk alert for a room with a humidity sensor (and an outdoor temperature of the house): the humidity at the coldest wall, by the method of DIN 4108-2 (wall at outdoor + 0.70 × (room − outdoor), Magnus formula), 80 % or more for an hour raises it, below 75 % it ends.

  • Visibility: a Decision sensor per room with the winning rule and the reason, an event on every change, diagnostics with the last 100 decisions and a Lovelace card with an editable schedule.

The complete guide, step by step and in plain words (every setting, every kind of heating, examples): docs/guide/README.md. The full specification is in docs/SPEC.md (Română).

Installation

HACS

  1. Search Smart Heating Control in HACS (the Marketplace from Home Assistant 2026.11), install it and restart Home Assistant.
  2. Not found? ⋮ → Custom repositories → add https://github.com/sandreialexandru/Smart-Heating-Control as Integration first.
  3. Settings → Devices & services → Add integration → Smart Heating Control.

Manual

Copy custom_components/advanced_climate into your config/custom_components folder and restart Home Assistant.

Requires Home Assistant 2026.6.0 or newer (the oldest version the tests run on; they also run on the newest one).

Configuration

Interactive configurator: docs/configurator.html walks through every form step by step, in English or Romanian, explains each choice and gives a summary of what to set. Download the file and open it in a browser.

  1. Create the house: first the temperature unit (°C or °F), then the name, people, nearby zones and the home rule, then the heating of the whole house (e.g. your Generic Thermostat). That is enough for a house heated by one thermostat: it becomes the zone Whole house and uses every option. It can be changed later in Configure → Heating of the whole house.
  2. Optionally add rooms with Add room on the integration page, for rooms with their own valves or thermostats. Each room has its own devices, sensors, windows and schedule. The zone Whole house is changed the same way (⋮ → Reconfigure on the integration page).
  3. Everything else is in the integration options (presence, workdays and calendar, weather and season, energy, heat source, manual changes and vacation, alerts).

Temperature unit

Each house has one temperature unit, °C or °F, for all its rooms. Every temperature of the house is entered and shown in it: the settings, the level temperatures, the sensors, the card and the set_override service. It is chosen first when the house is created and changed with Reconfigure on the integration page; the values are converted, nothing has to be entered again. The integration keeps its values in °C and converts the readings and commands of the thermostats and sensors from their own unit, so the unit of the house does not have to match the one of Home Assistant.

Every form shows only what applies. The choices come first; a second form then asks only for the values they need, and is skipped when nothing applies:

  • Heating: the source, then its devices (and the command for other thermostats), then the command settings: hysteresis, minimum times and Use the learned inertia for relays and on / off control (relays also need a room temperature sensor), the hysteresis for temperature / preset commands only when the thermostat does not report hvac_action, nothing for Generic Thermostat.
  • Rooms: TRV calibration and valve exercise only for TRVs; the fixed nearby temperature only with that choice; aggregation only with several temperature sensors; occupancy time only with occupancy sensors; window delays only with window sensors or the temperature-drop detection; the Schedule helper fields only for a helper; optimal start / stop limits only when turned on.
  • Options: preheat distances only with a Proximity / travel time sensor, cutoff / forecast / season / compensation values only for what is turned on, price and PV thresholds only with their sensors, heat source times only with a heat source, the fixed duration only for that kind of manual change.

Schedule format

One profile per line, each slot is HH:MM preset:

workday: 00:00 sleep, 06:00 home, 22:00 sleep
weekend: 00:00 sleep, 08:00 home, 23:00 sleep

Each profile has its days and is on or off (set in the card, Schedule): all days, workdays, weekend days and holidays, or chosen weekdays. A day uses, in this order: a calendar event titled with a profile name (also a profile that is off; an event that covers part of the day selects it for the whole day, today and the coming days alike, so the plan and the optimal start of tomorrow match what happens tomorrow) → the active profile of that weekday (e.g. a profile for Wednesday is above the workday profile on Wednesdays only) → the active profile of workdays or of weekend days → the active profile of all days. Turning a profile on turns off the active ones it overlaps (all days overlaps workdays and weekend days; chosen weekdays overlap when they share a day), so a day never has two.

A day no active profile covers keeps the frost protection; the room shows an alert (No active schedule profile: …) and the card warns before turning a profile on or off leaves such days. Profiles saved before 2.2 keep their days: mon … sun for their day, workday and weekend for their kind of day (for all days when the other one is missing), and when none of these exists the first profile is for all days; other profiles start off. The Profile select of the rooms was removed in 2.2.

How a room decides

Rules are evaluated from the top; the first one that applies wins:

  1. Safety (frost protection, maximum temperature) – always applied, also to a manual change and in pause (a level above the maximum is sent as the maximum); frost protection starts the heat source on its own
  2. Pause – only safety is sent (and a higher temperature left by heating by the room sensor is taken back to the target)
  3. Valve exercise – in every mode, not with a window open
  4. Mode Off / Summer / outside the heating season
  5. Window open
  6. Manual change
  7. Vacation (on a day without an active profile: frost protection)
  8. Presence: far → away (on a day without an active profile: frost protection), nearby → eco (or a fixed temperature; with Not above the schedule the lower of it and the schedule)
  9. Schedule (optimal start / stop, room occupancy)

Then the adjustments (outdoor cutoff, compensation, tariff, PV, solar gain) and the safety limits.

Entities

House: Mode (select), Presence (home / nearby / far), Pause and Guest mode (switches), Vacation start / end (datetime), Heating season, Outdoor cutoff and Heat demand (binary sensors), Outdoor average, Heating time, buttons to clear manual changes, clear the vacation and reevaluate.

Room: Decision (enum with the reason in the attributes), Target temperature, Room temperature, Next change, Heating rate, Cooling rate, Heating time, Heat demand, Window open, Manual change, Child lock (switch), Clear manual change, Reset learning (buttons) and, for rooms without Generic Thermostat, the level temperatures (numbers).

Learning

The full explanation, with worked examples and simulations: docs/learning.md.

Each room learns a small physical model of itself, continuously, with and without heating:

rise per hour = (heating − curve × outdoor) × q − loss × (room − outdoor) + sun gain × sun

  • Heating (heating_per_hour): °C per hour the heating adds at full heat, at 0 °C outdoors.
  • Weather curve (weather_curve): how many °C per hour more the heating adds for each °C colder outdoors: positive for a boiler with outdoor compensation, negative for a heat pump that gives less in the cold, 0 for a fixed water temperature or an electric heater. Learned once the room has heated at outdoor temperatures at least 1 °C apart (standard deviation); 0 until then and in a house without an outdoor temperature.
  • Heat loss (loss_per_hour): the part of the inside / outside difference lost per hour (colder outside, faster).
  • Sun gain (sun_gain): °C per hour the sun adds at a sun signal of 1. The signal is sin(sun elevation) × (1 − 0.75 × cloud cover^3.4), from the time, the location of Home Assistant and the clouds of the weather entity (0 at night, 1 with the sun overhead in a clear sky). Learned only with a weather entity and only when clearly seen (at least 5 standard errors from 0); 0 otherwise. No orientation to set.
  • Inertia (inertia_minutes): q, the part of the heating that reaches the room, follows the heating on / off with this delay: the boiler, the water, the radiators or the floor warm up first after a start and keep giving heat after a stop. It is learned, not set: ten candidates (0 – 240 minutes) are learned together and the one that predicts the room best is used.
  • Every 30 minutes of measurements is one equation; heating, curve, loss and sun gain are its least squares fit. Older stretches count less (half after 7 days), so the model follows a room that changes; a stretch far from what the model expects (more than 2.5 times the usual difference: a door left open, cooking) counts less.
  • Not used: stretches with a window or door sensor of the room (or a linked one) open, with the state of the heat source unknown, during the valve exercise, with the outdoor temperature unknown in a house that has one, or outside the cold season (mode Off or Summer, outside the heating season).
  • The model is used after 4 hours with heating and 4 without (usually within the first day); until then 60 minutes per degree, no inertia.
  • Without an outdoor temperature in the house the loss is learned as a constant (°C per hour).
  • All predictions (optimal start, time to target, optimal stop, the expected temperature at the change) are a minute by minute simulation of the model, from the room temperature and the heat reaching the room now.
  • The learning of versions before 2.6 (episodes) does not fit the model and is discarded: every room learns again after the update.
  • Heating only while the heat source runs. The learning (heating and cooling) and the heating time count a room as heating only while its heat source runs: Generic Thermostat heating (hvac_action), the relay or the on / off thermostat on, and, when a Heat source is set in the options (the boiler that TRVs and zone valves wait for), only while it runs too. A room that asks for heat while the heat source waits for other rooms cools, and is learned as heat loss. While the state of the heat source is unknown, nothing is learned. With TRVs and no heat source set the demand of the TRV is used; that is right for a boiler that runs all season or by outdoor compensation. With TRVs and a boiler started by a thermostat that is not in Home Assistant the learning is not reliable: optimal start and stop are not recommended.
  • The heat demand comes from hvac_action (heating). Thermostats that do not report it count as heating from the hysteresis below their set temperature until the hysteresis above it, like a relay (the optimal stop uses the hysteresis as its comfort too); the Hysteresis setting is shown for them (and for thermostats unavailable during the setup, which cannot be checked).

The Heating time sensors count the same way: a room while its heat source runs for it, the house while the heat source runs (without one, while at least one room heats). The chart of the card shows these periods.

The Heating rate sensor shows the minutes per degree with the heating on, at the room and outdoor temperatures of now; its attributes show the model (heating_per_hour, weather_curve, loss_per_hour, constant_loss, inertia_minutes, heat_reaching_now, error_per_hour), the minutes per degree at −10 / 0 / 10 / 20 °C outdoors and the learning progress (hours_heating, hours_idle, hours_needed). Optimal start uses the same model. With Rooms needed higher than 1, a room in optimal start waits until enough rooms ask for heat, so it may reach its target later.

While a room is below its target the card shows the time to the target (e.g. ~35 min) under the target temperature, from the model and the current outdoor temperature; until the model is learned it shows learning… with the default used under it (default 60 min/1°C). The Decision sensor has it as the time_to_target attribute (minutes).

Optimal stop

Optimal stop needs an outdoor temperature (sensor or weather entity of the house; without one the option is not shown and no optimal stop is made, and the outdoor values saved before are dropped). It lowers the level before the next colder one as early as the room can cool and still stay in the comfort of the current level at the scheduled time. The comfort is the tolerance: the cold tolerance of Generic Thermostat, the hysteresis for relays, on / off control and thermostats that do not report hvac_action, and the Optimal stop tolerance room setting for the other thermostats (default 0). Example: home 22 °C until 22:00, tolerance 0.5 °C, 7 °C outside: if the room falls from 22 to 21.5 °C in 40 minutes, sleep starts at 21:20.

  • The Maximum early stop room setting is the limit; until the model is learned the lower level starts that early.
  • How long the room can go without heat is simulated with the learned heat loss and inertia (warm radiators still give heat after the stop).
  • Once an optimal stop begins it continues until the scheduled time; the rules above the schedule can still override it. If the room falls below the comfort of the current level before that time (it cooled faster than learned), the optimal stop is cancelled: the current level stays until the scheduled time and the stop does not start again for that change. If this happens often, lower the Maximum early stop.
  • The card shows the expected temperature at the change (e.g. ~21.5° at 22:00), from the model and the outdoor temperature expected until then; the Decision sensor has it as the stop_forecast attribute.
  • The Cooling rate sensor shows how fast the room falls now without heating (empty until learned); its attributes show the loss, the inertia and the tolerance.

Outdoor forecast for optimal start / stop

With a weather entity that has an hourly forecast, the optimal start and the optimal stop use the outdoor temperature expected while they run, not the one of now. For a start at 05:00 for 07:00, the heating time is the one simulated with the mean forecast between 05:00 and 07:00; for a stop, the cooling uses the mean forecast of the stop period. The period depends on that temperature, so it is worked out again a few times (3 passes) from the period found before. Each forecast value holds for its hour; until the next forecast hour the measured outdoor temperature is used.

Without a weather entity, without an hourly forecast or when the forecast does not reach the change, the outdoor temperature of now is used, as before. The forecast is read every 30 minutes when the weather entity is set and the forecast cutoff or a room with optimal start / stop uses it.

The card shows the next optimal start or stop in the room Details (e.g. Start for preset home (21.0°) at 07:00: begins ~05:10, outdoor forecast 2.4°, or Start for temperature 21.0° at … when the level is sent as a temperature; running since … once it began; learning… until something is learned). The Decision sensor has it as the next_estimate attribute: kind (optimal_start / optimal_stop), at (the change), preset, minutes, starts_at, started_at, outdoor, outdoor_source (forecast / now), learned, sent_as (preset / temperature) and temperature (of the level). It is shown only when the option is on for the room and the next change is warmer (start) or colder (stop); the optimal stop also needs a known outdoor temperature and not to be cancelled for that change.

Services

Service Description
advanced_climate.set_override Set a preset or a temperature as a manual change (optional duration)
advanced_climate.clear_override Clear manual changes (one room or all)
advanced_climate.set_vacation Set or clear the vacation period
advanced_climate.reevaluate Evaluate everything now
advanced_climate.set_schedule Replace the schedule of a room (text or profiles)

Rooms are addressed by room (name or id) or by any of their entities.

The event advanced_climate_decision_changed is fired whenever a room changes its decision (room, old_rule, rule, old_target, target, reason).

Lovelace card

The integration adds the card to the dashboard resources automatically (/advanced_climate/smart-heating-control-card.js?v=<version>, updated on every release, so browsers and the companion app load the new version). With YAML-mode dashboards add that URL as a module resource yourself. The card has a visual editor. With no options it shows every house and room with every control:

type: custom:smart-heating-control-card
Option Default Shows
title Heating Card title (empty string hides it)
rooms all List of room Decision sensors to show
show_house true Presence and people (round badges in the colour of where they are), tiles for the outdoor average (over the Average over hours), season, heat demand and heating time, mode (Auto / Away / Vacation / Off / Summer), and a row of buttons: Pause and Guests (on / off; guest mode shows a band at the top), Vacation (opens the dates), Reevaluate, Automatic (clears all manual changes)
show_rooms true The rooms
show_timeline true A Chart button in every room that opens, in a window over the dashboard, the chart: 7 days of history and the next 12 hours, opened on the last 24 hours and the next 12: room temperature, the temperature the learned model predicts ahead (the heating switched as the device does: the GT tolerances, the hysteresis, the learned inertia; the target held for thermostats that regulate by themselves), target (colored by level), planned levels and the periods when the room heated. Hover, touch or drag on the chart to read the values (in an opaque box). Zoom with the buttons (1h, 6h, −, +), double-click, pinch or Ctrl + wheel, from 20 minutes up to the 7 days (⤢ goes back); move through the history by dragging the window in the navigation bar under the chart (shown while the mouse is over the chart or a finger is on it) or by scrolling sideways. Under the chart, every legend item hides or shows its series (kept in the browser). Once the room has learned that the sun warms it, the expected sun (sun_forecast, 0 to 1) is a faint yellow area in the outdoor band
show_quick_override true Set a level or a temperature for a number of hours (empty = the configured rule)
show_levels true Level temperatures (rooms without Generic Thermostat, fixed nearby temperature)
show_details true Room and target temperature, the learning (two progress bars while learning; then one tile each for heating, inertia, weather curve, sun and heat loss), heating time, active adjustments, level temperatures
show_schedule_editor true Schedule profiles with an editor: drag the start times on the day bar (5-minute steps), copy a profile over another one
collapsed false Rooms start folded (a row with a small arc, the name, the time to target, state icons, the level and the target); tap it to open the room
compact false One tile per room (the name, the status icons, arc with the temperature, level, target; under the name the time to target while heating, else the next change) and one row for the house; tap to open
runtime_period day Heating time shown for day, week or month (calendar periods, from the long-term statistics; tap the value in the card to change it). The Heating time sensors stay cumulative totals

Every room also shows its decision, a flame (outlined while it asks for heat, full and flickering while it heats; also on the house and on folded rooms) / window / manual change badges, an arc with the room temperature (empty at the frost protection, full at the maximum; it only shows the value), the target as a dot on it (the arc ends on the dot within 0.3 °C / 0.5 °F of the target), an arrow ↑ / ↓ in its opening while the room warms or cools (temperature_trend: at least 0.2 °C/h over the last 30 minutes) and the target, the reason, the time to target, heating by the room sensor when it is on, what the device itself measures, today's profile as a bar, and while there is a manual change a band with its end and an Automatic button (back to automatic) first in the row of buttons. Buttons under the arc (three per row) open For a while (set for a while; a manual change with an end shows the time it has left), Schedule (each profile with its days and an on / off switch; its days are chosen in the editor), Chart, Levels (level temperatures) and Details, each on its own (several at once), and a Lock button for the child lock of the room.

  • Not heating: below its target, a room says why it does not heat (within the thermostat tolerance or the hysteresis, a minimum on / off time, waiting for other rooms or the reference room, the heat source off or unknown, the thermostat off). The Decision sensor has it as no_heat_reason.
  • Warm outside: while the heating is off because it is warm the house shows why, e.g. Warm outside: on • heating is off until the average falls to 16°, on (forecast) • heating is off: the forecast mean for 3 h is 19.2°, or while the forecast lets the heating run cancelled (forecast) • it gets cold: the forecast mean for 3 h is 12.4°, rooms heat when they need it; the Outdoor average sensor has the cutoff_reason (measured, forecast_warm, forecast_cold) and the forecast_mean. It is not shown where the cutoff cannot act: mode Off or Summer, outside the heating season and in a pause (in Vacation it stays: away still heats).
  • Chart: the planned part follows what will happen: the schedule; a manual change for a set time until it ends; a planned vacation until its preheating and a calendar event until its end, then the schedule; a window, frost protection or the valve exercise only for now (the schedule ahead); mode Off / Summer, outside the season, pause, everyone away or nearby, failed sensors and warm outside as they are now, for the whole period.
  • Chart: the outdoor temperature in its own band (measured, then the hourly forecast dashed; the cutoff limit as a dotted line) and the next optimal start / stop as a shaded period with its start time (never longer than the room settings allow); in it the planned target is already the next level, and the tooltip shows Early start / Early stop above it.
  • Pause: a banner at the top of the card while the house is paused (the Pause switch stays the only control).
  • Alerts of the room and of the house in the open room, under the arc: a list with their number, each with a title, the text in the language of the card and a tap that opens its entity; the room is outlined red for an alert that something does not work, amber for the others.
  • Details, grouped: Temperatures (room, target, thermostat preset, humidity of the air and at the coldest wall with a humidity sensor, adjustments, level temperatures); Schedule (next optimal start / stop, heating time); Learning (its state or progress, with a Reset button that asks to confirm with a second click; once learned the heating: minutes per degree now and the inertia; the weather curve; the sun, once seen: its gain and what it adds now; the heat loss: how fast the room falls now).
  • Manual change: where it was made (card / service or on the device), until when, applies after: … while a higher rule keeps a change from the card off the devices, and comes back after: … while a higher rule interrupts it.
  • The next optimal start / stop is shown only while the room follows its schedule; cold rooms are reported only in those rooms.
  • Links: values, states, badges and details open the more-info dialog of their entity.
  • Language: the reason of the decision and the names of the adjustments are shown in the language of the card (the Decision sensor has them as reason_key and reason_params; reason stays the English text).