diff --git a/Buildings/Fluid/HeatExchangers/DryCoilCounterFlow.mo b/Buildings/Fluid/HeatExchangers/DryCoilCounterFlow.mo index 4262e378a5d..3196c2e98ad 100644 --- a/Buildings/Fluid/HeatExchangers/DryCoilCounterFlow.mo +++ b/Buildings/Fluid/HeatExchangers/DryCoilCounterFlow.mo @@ -45,8 +45,8 @@ model DryCoilCounterFlow "Set to false to make air-side hA independent of temperature" annotation (Dialog(tab="Heat transfer")); - parameter Modelica.Units.SI.ThermalConductance GDif=1E-2*UA_nominal/(nEle - 1) - "Thermal conductance to approximate diffusion (which improves model at near-zero flow rates" + parameter Modelica.Units.SI.ThermalConductance GDif=1E-2*UA_nominal/max(1, (nEle - 1)) + "Thermal conductance to approximate diffusion (which improves model at near-zero flow rates)" annotation (Dialog(tab="Experimental")); Modelica.Units.SI.HeatFlowRate Q1_flow=sum(ele[i].Q1_flow for i in 1:nEle) "Heat transferred from solid into medium 1";